Skip to content Skip to footer

Multi-Turn Intelligent Electric Actuator BD301-IIC

  • Power supply: three-phase: 380Vac±10% 50Hz±2%; single phase: 220Vac±10% 50Hz±2%
  • Input signal: DC4-20mA; dry contact; DC24V and AC220V pulse and electric frequency signals
  • Output signal: DC4-20mA; 4 groups of bistable output contacts configurable in the field, 1 group of monostable output contacts for remote instruction, and 1 group of monostable output contacts of fault alarm.
  • Output contact capacity: 250Vac/5A or 30Vdc/5A
  • Output current load impedance: ≤750Ω
  • Ambient temperature: -30°C- +70°C
  • Protection class: IP68
  • Flange standard: ISO 5210:2017 (GB/T12222-2023)
  • Explosion-proof marking: Ex db IIC T4 Gb; Ex tb IIIC T130℃ Db 
  • Approvals (optional): ATEX, IECEx, CSA (available on request with longer lead time).

Description

Multi-Turn Intelligent Electric Actuator Overview

You can integrate the BD301-IIC multi-turn intelligent electric actuator into any automation network because Suzhou Bonray designed it with multiple control modes and fieldbus options. This multi-turn intelligent actuator accepts analog (4‑20 mA), digital (Profibus‑DP, Modbus, HART, DeviceNet, FF), and dry‑contact signals. The factory‑built non‑intrusive interface lets you configure parameters using a magnetic knob or infrared tool. The multi-turn intelligent actuator displays valve position, torque, and alarm messages on a high‑visibility LCD. With IP68 dual sealing and explosion‑proof variants, this device works reliably in wet, dusty, or hazardous areas. Whether you need remote manual control, automatic positioning, or ESD override, the BD301‑IIC multi-turn intelligent electric actuator gives you total command.

Fieldbus Cards
Fieldbus Cards

How many control modes does this multi-turn intelligent electric actuator support?

Seven modes: field local (inching/hold), remote switching (point/hold), remote analog (4‑20 mA automatic), ESD, fieldbus digital, two‑wire (signal‑open/signal‑close), and intermittent operation.

Multi-Turn Intelligent Electric Actuator Features

Seven Control Modes in One Device

  • Field control: Use the rotary knob or infrared setter for local inching or hold.

  • Remote switching: Three inputs (open, close, stop/hold) for manual remote.

  • Remote analog: 4‑20 mA for automatic positioning.

  • ESD: Overrides all other commands.

  • Fieldbus: Profibus, Modbus, etc. for digital networks.

  • Two‑wire: “Signal open / no‑signal close” or reverse logic.

  • Intermittent: Start‑stop motion to prevent fluid hammer.

Absolute Encoder
Absolute Encoder

Absolute Encoding Sensors
The multi-turn intelligent actuator uses a BM18 multi‑turn absolute encoder for position and a separate absolute encoder for torque. Both use non‑contact technology, so they never wear out and do not need batteries.

Automatic Phase Correction
You do not worry about phase sequence. The actuator detects incoming phase rotation and corrects it internally. This feature also protects the multi-turn intelligent actuator from phase loss.

Configurable Relay Outputs
Four S‑series bistable relays (S1‑S4) and optional R‑series monostable relays (R1‑R4) let you send valve status (open/close, torque, moving, mid‑position) to your control room. You set each contact’s behavior via the menu.

ESD with Priority Logic
You decide the ESD action: open, close, or lock. You also choose whether ESD overrides motor thermal protection. The multi-turn intelligent electric actuator responds instantly to emergency signals.

Model and Type

The BD301-IIC on-off multi-turn intelligent electric actuator lacks proportional control and is permitted only under the following conditions: operating frequency ≤ 60 cycles per hour, single continuous operation duration ≤ 15 minutes, and operating duty cycle ≤ 33.3%.

The BD301-IIC intermittent modulating multi-turn intelligent electric actuator features proportional control. Its applicable conditions are: operating frequency ≤ 60 cycles per hour (for three-phase models, the short-term operating frequency can reach up to 600 cycles per hour), continuous operation time ≤ 15 minutes, and duty cycle ≤ 33.3%.

Schematic diagram of BDBDM-IIC outline dimensions
Schematic diagram of BDBDM-IIC outline dimensions

Specifications

ParameterValue
Input signal impedance250 Ω (for 4‑20 mA).
Analog setpoint accuracy±1% of span.
Deadband (adjustable)0.5% to 10% of span.
Output current load≤750 Ω for 4‑20 mA feedback.
Relay capacity5 A / 250 Vac or 5 A / 30 Vdc (resistive).
Bistable relay memoryRetains state after power loss.
Alarm relay (MONI)Triggers on phase loss, overheat, signal loss, ESD active, internal fault.
IsolationOpto‑isolated I/O channels.
Operating humidity≤95% RH (non‑condensing).

Data sheet

BD301-IICThree Phase
Output Speed (rpm)Rated Torque (N.m)Motor Power (KW)Rated Current (A) Locked Rotor Current(A)
482500720108
721800720108
961300720108
144900720108